Current position:
Product characteristics The 0.6/1kV extruded insulated power cable produced by Shandong Yanggu Wanlixing Cable is fixed and laid at AC 50Hz
Product details

1、 Product execution standards

1. GB/T 12706.1-2020 Power cables with extruded insulation and accessories for rated voltages from 1kV (Um=1.2kV) to 35kV (Um=40.5kV) - Part 1: Cables with rated voltages of 1kV (Um=1.2kV) and 3kV (Um=3.6kV)

2. GB/T 19666-2019 General rules for flame retardant and fire-resistant cables (applicable only to flame retardant and fire-resistant cables)

2、 Product features

1. Usage conditions

Rated working voltage: 0.6/1 (1.2) kV;

Cable laying temperature: ≥ 0 ℃;

The maximum long-term working temperature allowed for cable conductors: PVC insulation: 70 ℃, XLPE insulation: 90 ℃;

The maximum working temperature of the cable during short circuit (maximum 5 seconds): XLPE insulation at 250 ℃; PVC insulation: cross-sectional area ≤ 300mm ², 160 ℃, cross-sectional area>300mm ², 140 ℃;

The minimum allowable bending radius of cables: 20D for single core without armor, 15D for single core with armor, 15D for three core without armor, and 12D for three core with armor. Note: D represents the actual outer diameter of the cable.

2. Structural requirements

The basic structure of a 1kV extruded insulated power cable consists of three parts: conductor, insulation layer, and protective layer.

1) Conductors

The conductor is made of twisted copper or aluminum wire, which meets the requirements of GB/T 3956-2008 standard. A conductor is the conductive part of a power cable used to transport electrical energy

2) Insulation

Insulation is extruded using PVC or XLPE. Electrically isolate the wire cores from the ground and wires of different phases to ensure the transmission of electrical energy.

3) Outer sheath

The outer sheath is made of PE or PVC, and materials such as flame retardant, anti termite, low smoke low halogen flame retardant, and low smoke halogen-free flame retardant can also be provided according to customer requirements. The function is to protect power cables from external impurities and moisture intrusion, as well as prevent direct damage to power cables by external forces.

3、 The structural diagram of 1kV extruded insulated power cable is as follows.



4、 Model description of 1kV extruded insulated power cable

Product code (omitted)

Characteristic code WDZ - Low smoke halogen-free flame retardant; ZA (ZB, ZC) - flame retardant (A, B, C) level; NH - refractory;

Conductor material code

The second type of copper conductor - (T) is omitted; Type 5 copper conductor - R; Aluminum Conductor-L

Insulation material code

YJ cross-linked polyethylene insulation; V-PVC insulation; E-ethylene propylene rubber insulation; EY - Hard EPDM Rubber Insulation

Sheath material code

V-PVC sheath; Y-polyethylene or polyolefin sheath; F-elastic sheath; Q-lead sleeve

Armor material code

2- Double steel strip armor; 3- Fine round steel wire armor; 4-Coarse round steel wire armor; 6- (Dual) Non magnetic metal tape armor; 7-Non magnetic metal wire armor

Material code for outer sheath

2-Polyvinyl chloride sheath; 3- Polyethylene or polyolefin sheath; 4-Elastomer sheath

Common models

Model

name

Installation occasions

Copper core

Aluminum core

YJV

YJLV

Crosslinked polyethylene insulated polyvinyl chloride sheathed power cables

Can be laid indoors, in tunnels, and in pipelines

YJY

YJLY

Crosslinked polyethylene insulated polyethylene sheathed power cables

YJV22

YJLV22

Crosslinked polyethylene insulated steel strip armored polyvinyl chloride sheathed power cable

Suitable for buried laying and unsuitable for laying inside pipelines

YJV23

YJLV23

Crosslinked polyethylene insulated steel strip armored polyethylene sheathed power cable